UNDERWRITERS LABORATORIES INC. APPLIANCE WIRING MATERIAL Subj. 758 Section 1 Page 1031 Issued: May 1, 1959 Revised: Oct. 23, 2000
Style 1031 PVC Insulated Wire.
______________________________________________________________________________
Rating 80 deg. C, 1000 V ac and/or 1200 V dc.
______________________________________________________________________________
*Conductor No. 30-9 AWG. Solid or stranded, tinned or bare copper.
______________________________________________________________________________
Insulation 30 mils minimum average, 27 mils minimum at any point of PVC.
______________________________________________________________________________
*Covering Extruded Nylon in 2 mil minimum thickness or * Lacquered Braid.
______________________________________________________________________________
*Standard Appliance Wiring Material UL 758.
______________________________________________________________________________
Instructions Detailed Examination. to UL Tensile Strength and Elongation of Insulation, *Representative same as for Class 43. * Spark Test.
______________________________________________________________________________
UL (4) Detailed Examination.
*Counter-Check (4) Tensile Strength and Elongation of Insulation. *Program (4) Heat Shock. * (4) Deformation. * (4) Cold Bend. * (4) Horizontal Flame Test.
______________________________________________________________________________
*Marking General.
______________________________________________________________________________
Use Internal Wiring of Appliances; or Internal Wiring of Appliances where exposed to oil at a temperature not exceeding 60 or 80 deg. C (whichever is applicable). Tags may also indicate the following: 3500 V peak - For electronic use only.
______________________________________________________________________________